  • LZZB9-40-188(CQ).jpg

LZZB9-40-188(CQ)


LZZB9-40-188(CQ)

Model Code
L
Z
Z
B
9 40 188
CQ
Encoding content
Current transformer
Pillar
pouring type
With protection level
Design serial number
Maximum voltage of equipment
Width
Structure code
Indoor LZZB9-40-188(CQ) type epoxy resin cast insulation pillar type fully enclosed current transformer, suitable for power measurement, current detection and relay protection within 35kV and AC 50/60Hz, suitable for SF6 gas insulated switchgear.

Technical parameters


Rated primary current (A) Rated secondary current (A) Accurate Level Combination Capacity (VA) Rated short-time thermal current (kA/s) Rated dynamic stability current (kA)
100、200、300、400 1(5) 0.2S/5P20 5/5 25 ka/1s 63
600、750、800 1(5) 0.2S/0.5/5P10 10/10/10 25 ka/3s 63
1000、1200、1250、1500 1(5) 0.2S/0.5/5P15 15/15/15 31.5 Ka/4S 80
2000、2500 1(5) 0.2S/0.5/5P20 20/20/20 31.5kA/4s 80

Products meet the standard GB20840.1, GB20840.2, IEC61869-1, IEC61869-2

If users have special requirements, they can be determined after consultation with our company.

The above technical parameters are not the final technical commitment, please be confirmed by our technical personnel.

Product Information


Product Description

Indoor LZZB9-40-188(CQ) type epoxy resin cast insulation pillar type fully enclosed current transformer, suitable for power measurement, current detection and relay protection within 35kV and AC 50/60Hz, suitable for SF6 gas insulated switchgear.

Conditions of use

Installation location: indoor.

Ambient temperature:-25 ℃ ~ 40 ℃, daily average temperature is not more than 30 ℃.

Altitude: ≤ 1000m, higher altitude can be selected as required.

Humidity: The maximum relative humidity at room temperature is 95%.

There shall be no violent vibration or collision at the installation site.

Structural Overview

Pillar type, totally enclosed. Epoxy resin cast insulated current transformer.

The primary end is identified as P1-P2, and the secondary end is identified as 1S1-1S2,2S1-2S2...... This model has 16 secondary terminals and supports up to 4 secondary windings.

Technical Data

The installation site is free of gas, steam, chemical deposition, explosion and corrosive media that seriously affect the insulation of the transformer.

The electric voltage of the equipment is 35kV, and the maximum operating voltage is 40.5kV. Power frequency withstand voltage of 1. secondary winding and grounding 95kV/60s

Power frequency withstand voltage between secondary windings and grounding 3kV/1min.

Lightning impulse withstand voltage 200 kV.

Other requirements shall be in accordance with GB20840.1, GB20840.2, IEC61869-1 and IEC61869-2.

Application Case


Outdoor transformer application case

Outdoor transformer application case

Outdoor transformer application case

Outdoor transformer application case

Outdoor transformer application case

Outdoor transformer application case

Outdoor transformer application case

Outdoor transformer application case